A liquid-cooled, 690 V grid-forming PCS for front-of-meter storage. Three units form a 1.35 MW AC block; six form 2.7 MW — stepped up through a medium-voltage transformer.

Peak conversion efficiency
DC operating range starts at 700 V — cabinet configurations stay at full power longer
NEMA Type 4X / IP66 liquid-cooled outdoor enclosure
Largest standard AC block (6 × P450)
| Rated power | 450 kW / 495 kVA @ 45 °C |
|---|---|
| Grid connection | 690 Vac, 3P3W + PE, 60 Hz (via MV step-up transformer) |
| Max. DC voltage | 1500 V |
| Battery voltage range | 700–1500 V operating; full rated power from 800 V |
| Max. DC current | 560 A |
| Max. DC power | 500 kW |
| Peak efficiency | 98.5% |
| Output THDi | < 3% at rated power |
| Grid-forming | Standard — voltage-source behavior, inertia response, phase-jump ride-through, black start (UNIFI V3 aligned) |
| Cooling | Liquid cooling |
| Enclosure | NEMA Type 4X / IP66, outdoor installation |
| Noise | ≤ 65 dB(A) @ 1 m at rated operation |
| Communications | Ethernet, RS485, CAN — Modbus TCP / RTU, CAN 2.0, IEEE 2030.5 (CSIP) |
| AC blocks | 1.35 MW (3 × P450) · 2.7 MW (6 × P450), MV transformer integrated |
| Cell compatibility | 314 Ah, 587 Ah and 648 Ah LFP systems in standard series configurations |
| Certification | Designed to UL 1741 (incl. SB) and IEEE 1547; certification testing in progress — status available on request |
Specifications are design targets for the production configuration and subject to change without notice.
Full datasheets, single-line diagrams and the certification roadmap are available under NDA for qualified projects.
Request the Datasheet